Job No: TR-2026-0002 PASS

OCF 02 • Odur control extract fan motor

Hydrotek Engineering Co.

Hydrotek Engineering Co.

Technical Services Division

Technical Services Division
EQUIPMENT OVERHAUL & TEST REPORT
Job No: TR-2026-0002
Date: 12/05/2026
Overall Result: PASS
1. Equipment Details
Project Details Mushrif pumping station rehabilitation work
Tag / Equipment ID OCF 02 Location ML-1
Equipment Name Odur control extract fan motor
Motor Specs 160 kW | 415 V | 261.9 A
2. Electrical & Insulation Checks
Test Parameter Measured Value Result
Motor Rewinding & Stator Check REPLACED AND TESTED OK PASS
Winding Resistance (Ohms) U–V: 0.121 Ω | V–W: 0.119 Ω | W–U: 0.120 Ω PASS
Insulation Resistance (500V DC) – Phase to Ground 441.11 MΩ (Min: > 5 MΩ) PASS
Insulation Resistance (500V DC) – Phase to Phase 433.63 MΩ (Min: > 5 MΩ) PASS
3. Mechanical Seal & Bearing Replacement
Component Checked Replacement Details / Part No. Result
Bearings – Drive End (DE) Part No: 6316 C3 • Brand: SKF (Explorer Series) (Replaced New) PASS
Bearings – Non-Drive End (NDE) Part No: 6314 C3 • Brand: SKF (Explorer Series) (Replaced New) PASS
Mechanical Seal & Leak Test N/A (Fan Motor Drive) • Static Leak Test: N/A PASS
4. Operational Run Test
Test Parameter Measured Value Result
Running Current (A) L1: 91.30 A | L2: 93.13 A | L3: 89.47 A PASS
Bearing Temperature (°C) DE: 51.5 °C | NDE: 43.2 °C (Normal) PASS
Vibration Level DE: 1.60 mm/s | NDE: 1.68 mm/s (Smooth) PASS
Rotation & Seal Check Rotation: Correct (CW) | Seal Leakage: Nil / None PASS
5. Sign-Off & Approvals
PREPARED BY:
ENG. JITHU THOMAS
Signature Date: 12/05/2026
INSPECTED BY:
ASWATH KUMAR HOSDURG
Signature Date: 12/05/2026
APPROVED BY:
ABU GEROGE
Signature Date: 12/05/2026
Hydrotek Engineering Co. • Equipment Overhaul & Test Certificate