Job No: HY-TSD-TR-2026-0640 ACCEPTED

SV404F07T/2 • Vertical Multistage In-Line Booster Pump • Mishref Station

Hydrotek Engineering Co.

Hydrotek Engineering Co.

Technical Services Division

Technical Services Division
BOOSTER PUMP OVERHAUL & TEST REPORT
Job / WO No: HY-TSD-TR-2026-0640
Report No: HY-TSD-TR-2026-0640
Date:
Result: ACCEPTED
1. Equipment Details
Project Details Mishref Station (Ministry of Public Works (MPW))
Tag / Equipment ID SV404F07T/2 Location Main Building - Roof
Equipment Name Vertical Multistage In-Line Booster Pump (Vertical Multistage In-Line Booster Pump)
Motor Specs 0.7 kW (1 HP) | 415 V | 1.70 A | 2900 RPM RPM
Pump Specs Model: LOWARA SV404F07T/2 | Flow: 8 m³/hr | Head: 34 m m
Booster Specs Suction: 1.00 Bar | Discharge: 3.40 Bar | Boost Head: 25.00 m | Stages: 4 | Hydro Test: 3.40 Bar
2. 1. ELECTRICAL & STATOR INSULATION TEST
Test Parameter Measured Value Result
Stator Condition / Winding Status Overhauled, Serviced & Tested OK PASS
Winding Resistance (U1-U2, V1-V2, W1-W2 in Ohms) U1–U2: 15.236 Ω | V1–V2: 15.205 Ω | W1–W2: 14.998 Ω PASS
Insulation Resistance (500V DC) – Phase to Ground U–G: 439.95 MΩ | V–G: 449.51 MΩ | W–G: 433.67 MΩ PASS
Insulation Resistance (500V DC) – Phase to Phase U–V: 434.70 MΩ | V–W: 443.30 MΩ | W–U: 421.50 MΩ PASS
3. 2. MECHANICAL SPECIFICATIONS & RENEWALS
Component Checked Replacement Details / Part No. Result
Drive End (DE) Bearing Fitted Part No: 6203 • Brand: SKF (Replaced New) PASS
Non-Drive End (NDE) Bearing Fitted Part No: 6202 • Brand: SKF (Replaced New) PASS
Mechanical Seal / Seal Spec Cartridge Balanced Mechanical Seal (EPDM) • Static Leak Test: PASS PASS
4. 3. HYDRAULIC & HYDROSTATIC PRESSURE TESTING
Test Parameter Measured Value / Verification Result
Hydraulic Pressure Boost Head Suction: 1.00 Bar • Discharge: 3.40 Bar • Boost Head: 25.00 m • Stages: 4 PASS
Hydrostatic Pressure Hold Test Pressure: 3.40 Bar • Duration: 30 mins • Integrity: PASS - Zero Leakage PASS
Pressure Controls & Transducer Cut-In: 2 Bar • Cut-Out: 3.4 Bar PASS
5. 4. OPERATIONAL RUN TEST (NO-LOAD / FULL SYSTEM RUN)
Test Parameter Measured Value Result
Running Current (A) L1: 0.6 A | L2: 0.6 A | L3: 0.6 A PASS
Bearing Temperature (°C) DE: 48.5 °C | NDE: 43.2 °C (Normal) PASS
Vibration Level DE: 1.55 mm/s | NDE: 1.68 mm/s (Smooth) PASS
Rotation & Seal Check Rotation: Correct (CW) | Seal Leakage: Nil / None PASS
6. 5. SPECIALIZED WORKSHOP VERIFICATIONS
Test Name Standard / Criteria Measured / Inspection Result
Hydrostatic Pressure Shell Test 1.5x Design Pressure (15 mins) No leakage or drop observed PASS
Control Panel & PLC - Calibrated and No Fluctuation found PASS
Pressure Tank 200ltr 10 bar - No leakage or drop observed PASS
7. Sign-Off & Approvals
TESTED & OVERHAULED BY
ENG. JITHU THOMAS
Signature Date: 23/09/2026
QA / QC ENGINEER
ASWATH KUMAR HOSDURG
Signature Date: 23/09/2026
HEAD OF DIVISION / WORKSHOP MANAGER
ABU GEROGE
Signature Date: 23/09/2026
Hydrotek Engineering Co. • Custom Equipment Overhaul & Test Certificate
REF: HY-TSD-TR-2026-0640 • PAGE 1 OF 1

Equipment Photographic Documentation & Overhaul Audit 0 photo(s)

Visual proof of equipment condition: Intake / Before Overhaul vs. Completed / After Overhaul.

1. Intake / Before Overhaul Condition

0 photos

Photographs taken upon arrival (nameplate, casing, impeller wear, physical damage).

No intake condition photographs uploaded yet.

2. Completed / Post-Overhaul Condition

0 photos

Photographs taken after reassembly, painting, rewinding, new bearings & test run.

No completion photographs uploaded yet.