Facility Maintenance • Kuwait
Mishref Pump Room Overhaul Schedule
Hydrotek Engineering Co. Technical Services Division • Real-time motor rewinding, mechanical overhaul tracking, and standardized test certification.
Total Equipment
66
Pumps & Motors
Completed
66
100% rate
Delivered
66
To Mishref Room
Certificates Ready
66
QC Signed
Equipment & Motor Repair Records 66
Showing page 4 of 5| Sr. | Tag No • Location | Equipment Details & Power | Initial Status & Scope | Progress / Remarks | Test Certificate | Actions |
|---|---|---|---|---|---|---|
| 46 |
SP 4
LL
Qty: 1 unit
|
Sump pump Flygt 3057.181
1.7KW, 3PH, 415V
|
Condition: Motor submerged in water Winding is faulty
Complete dismantling, Cleaning, rewinding of stator, Replacenemt of DE, NDE...
|
COMPLETED AND DELIVERED
|
||
| 47 |
SP 05
LL
Qty: 1 unit
|
Sump pump Flygt 3057.181
1.7KW, 3PH, 415V
|
Condition: Motor submerged in water Winding is faulty
Complete dismantling, Cleaning, rewinding of stator, Replacenemt of DE, NDE...
|
COMPLETED AND DELIVERED
|
||
| 48 |
SF 03
LL
Qty: 1 unit
|
Smoke Exhaust Fan
15KW, 3PH, 415V
|
Condition: Motor submerged in water
Complete dismantling, Cleaning, Drying of stator winding, Replacenemt of DE...
|
17 May 2026
COMPLETED AND DELIVERED
|
||
| 49 |
SF 04
LL
Qty: 1 unit
|
Smoke Exhaust Fan
15KW, 3PH, 415V
|
Condition: Motor submerged in water
Complete dismantling, Cleaning, Drying of stator winding, Replacenemt of DE...
|
17 May 2026
COMPLETED AND DELIVERED
|
||
| 50 |
SF 07
LL
Qty: 1 unit
|
Smoke Exhaust Fan
11KW, 3PH, 415V
|
Condition: Motor submerged in water
Complete dismantling, Cleaning, Drying of stator winding, Replacenemt of DE...
|
17 May 2026
COMPLETED AND DELIVERED
|
||
| 51 |
SF 08
LL
Qty: 1 unit
|
Smoke Exhaust Fan
11KW, 3PH, 415V
|
Condition: Motor submerged in water
Complete dismantling, Cleaning, Drying of stator winding, Replacenemt of DE...
|
17 May 2026
COMPLETED AND DELIVERED
|
||
| 52 |
No tag
Qty: 1 unit
|
Smoke Exhaust Fan
1.1KW, 3PH, 415V
|
Condition: Motor submerged in water
Complete dismantling, Cleaning, Drying of stator winding, Replacenemt of DE...
|
23 Apr 2026
COMPLETED AND DELIVERED
|
||
| 53 |
No tag
Qty: 1 unit
|
Smoke Exhaust Fan
5.5KW, 3PH, 415V
|
Condition: Motor submerged in water
Complete dismantling, Cleaning, Drying of stator winding, Replacenemt of DE...
|
23 Apr 2026
COMPLETED AND DELIVERED
|
||
| 54 |
NA
NA
Qty: 1 unit
|
Fountain pump 1
2.6KW, 1PH, 230V
|
Condition: motor and pump submerged in water.
Complete dismantling, Cleaning, Drying of stator winding, Replacement of DE...
|
COMPLETED AND DELIVERED
|
||
| 55 |
NA
NA
Qty: 1 unit
|
Fountain pump 2
2.6KW, 1PH, 230V
|
Condition: motor and pump submerged in water.
Complete dismantling, Cleaning, Drying of stator winding, Replacement of DE...
|
COMPLETED AND DELIVERED
|
||
| 56 |
NA
NA
Qty: 1 unit
|
Horizontal pump
4.7KW, 3PH, 415V
|
Condition: Motor and pump submerged in water
Complete dismantling, Cleaning, Drying of stator winding, Replacement of DE...
|
COMPLETED AND DELIVERED
|
||
| 57 |
NA
NA
Qty: 1 unit
|
Sump pump 1 Flygt 3057.181
4.7KW, 3PH, 415V
|
Condition: Motor submerged in water
(among this one pump already repaired an...
Complete dismantling, Cleaning, Drying of stator winding, Replacement of DE...
|
COMPLETED AND DELIVERED
|
||
| 58 |
NA
NA
Qty: 1 unit
|
Sump pump 2 Flygt 3057.181
4.7KW, 3PH, 415V
|
Condition: Motor submerged in water
(among this one pump already repaired an...
Complete dismantling, Cleaning, Drying of stator winding, Replacement of DE...
|
COMPLETED AND DELIVERED
|
||
| 59 |
NA
NA
Qty: 1 unit
|
Sump pump 3 Flygt 3057.181
4.7KW, 3PH, 415V
|
Condition: Motor submerged in water
(among this one pump already repaired an...
Complete dismantling, Cleaning, Drying of stator winding, Replacement of DE...
|
COMPLETED AND DELIVERED
|
||
| 60 |
NA
NA
Qty: 1 unit
|
Sump pump 4 Flygt 3057.181
4.7KW, 3PH, 415V
|
Condition: Motor submerged in water
(among this one pump already repaired an...
Complete dismantling, Cleaning, Drying of stator winding, Replacement of DE...
|
COMPLETED AND DELIVERED
|
Showing 46 to 60 of 66 units
Remove Testing Data
Clear data to upload & process new Excel